Thanks again @gdluck for the log! We conducted a thorough protocol trace analysis on the 315 log events and identified exactly why the start was so painful, and opened PR #675 with a fix + authentic trace fixture.
Why was the start so slow (~2.7 minutes of timeouts)?
Your friend's installation has 16 heating zones (zones 35 to 50) and an F455 gateway:
Protocol Asymmetry Between Gateways:
In standard OpenWebNet WHO 4 (WHO_4 2.pdf), dimension-less status requests *#4*WHERE## are only defined for WHERE = 0 (general plant sweep) and WHERE = #0 (central unit). Individual zone status requests *#4*Z## (zones 1..99) are not part of the standard SCS bus protocol.
Physical thermostats (LN4691, 3550, etc.) on the SCS bus have no telegram handler for dimension-less *#4*Z##.
On physical bridge gateways (F455, F454, MH200N, MH202), incoming command frames are forwarded directly to the SCS bus. Because the bus is silent, the gateway sends no response back to Home Assistant.
When Home Assistant loaded the 16 climate entities at startup, it scheduled status polls for each zone (*#4*35##, *#4*36##, etc.).
OWNd command session waited COMMAND_TIMEOUT = 10 seconds per request.
After 10.08 seconds of silence: WARNING (MainThread) [custom_components.myhome] [F455 gateway - 192.168.1.136] Timed out awaiting the complete response for '*#4*35##'; command session closed.
OWNd had to drop the socket, re-establish a TCP connection, complete HMAC-SHA256 authentication, and then attempt the next zone query.
For 16 zones: 16 × 10.08 s = 161.3 seconds (~2.7 minutes) of serial timeouts locking up command queue 0! Any light or cover command sent during this period was stuck in line.
Spontaneous Telemetry Was Already Received:
The trace shows that upon startup, the general sweep *#4*0## was sent and the physical thermostats broadcasted their full state spontaneously on the monitor session (dimensions 0, 12, 13, 14, 19, 20).
Thus, individual *#4*Z## point-to-point queries were not only failing, but completely redundant.
Identified physical gateways (F455, F454, MH200, MH201, MH202, etc.) via a new supports_zone_status property.
Disabled _poll_on_add and point-to-point async_update() status requests on physical gateways, relying on the startup sweep and spontaneous monitor updates instead.
Added the authentic F455 trace fixture and deterministic replay test suite in tests/test_issue_674_f455_climate_trace.py.
Activity
GreenGrassBlueOcean commentedon Oct 9, 2026
thanks for the trace!!
gdluck commentedon Oct 9, 2026
Now its stable, but the start was awful
GreenGrassBlueOcean commentedon Oct 9, 2026
f455 is terrible gateway
GreenGrassBlueOcean commentedon Oct 9, 2026
Thanks again @gdluck for the log! We conducted a thorough protocol trace analysis on the 315 log events and identified exactly why the start was so painful, and opened PR #675 with a fix + authentic trace fixture.
Why was the start so slow (~2.7 minutes of timeouts)?
Your friend's installation has 16 heating zones (zones 35 to 50) and an F455 gateway:
Protocol Asymmetry Between Gateways:
WHO_4 2.pdf), dimension-less status requests*#4*WHERE##are only defined forWHERE = 0(general plant sweep) andWHERE = #0(central unit). Individual zone status requests*#4*Z##(zones 1..99) are not part of the standard SCS bus protocol.*#4*Z##.bt_luci) intercepts*#4*Z##and replies directly from its internal cache with dimensions*#4*Z*0*...##,*#4*Z*12*...##,*#4*Z*14*...##, etc.The 160-Second Serial Timeout Cascade:
*#4*35##,*#4*36##, etc.).OWNdcommand session waitedCOMMAND_TIMEOUT = 10seconds per request.WARNING (MainThread) [custom_components.myhome] [F455 gateway - 192.168.1.136] Timed out awaiting the complete response for '*#4*35##'; command session closed.Spontaneous Telemetry Was Already Received:
*#4*0##was sent and the physical thermostats broadcasted their full state spontaneously on the monitor session (dimensions 0, 12, 13, 14, 19, 20).*#4*Z##point-to-point queries were not only failing, but completely redundant.The Fix (PR #675)
F455,F454,MH200,MH201,MH202, etc.) via a newsupports_zone_statusproperty._poll_on_addand point-to-pointasync_update()status requests on physical gateways, relying on the startup sweep and spontaneous monitor updates instead.tests/test_issue_674_f455_climate_trace.py.fix(climate): eliminate 10s command session timeouts on F455 and phys…
fix(climate): eliminate 10s command session timeouts on F455 and phys…
test(climate): fix F455 replay dispatcher signal and enforce strict s…
Merge pull request #675 from OpenWebNet-HA/test/issue-674-f455-climat…
fix(gateway): skip the startup requests the firmware refuses, poll ea…
fix(gateway): skip the startup requests the firmware refuses, poll ea…
fix(gateway): skip the startup requests the firmware refuses, poll ea…
fix(gateway): skip the startup requests the firmware refuses, poll ea…
fix(climate): hold the setpoint in force only on gateways that answer *…
fix(gateway): skip the startup requests the firmware refuses, poll ea…
fix(gateway): treat the F450 as SCS-only and keep the F460 on the zon…
fix(gateway): skip the startup requests the firmware refuses, poll ea…
fix(gateway): treat the F450 as SCS-only and keep the F460 on the zon…
docs(climate): correct the *michnovka#4*Z## and *michnovka#4*Z*0## ex…
docs(climate): do not claim the refusing gateways push humidity upward (
test(climate): replay each humidity capture on its own gateway throug…
fix(gateway): skip the startup requests the firmware refuses, poll ea…
fix(gateway): treat the F450 as SCS-only and keep the F460 on the zon…
docs(climate): correct the *michnovka#4*Z## and *michnovka#4*Z*0## ex…
fix(gateway): skip the startup requests the firmware refuses, poll ea…
fix(gateway): treat the F450 as SCS-only and keep the F460 on the zon…
docs(climate): correct the *michnovka#4*Z## and *michnovka#4*Z*0## ex…