Covers: end a timed run at the stop status, not the stop write (#466) #705

Closed

Description

@GreenGrassBlueOcean

Follow-up from the review of #647 (replaced by #702).

Problem

A timed run is anchored at the direction echo and ended at the stop write (cover.py: _auto_stop, _track_write, _freeze_position). The motor runs from the relay switching on until the stop frame reaches the relay, so the booked run can be shorter than the real one.

Measured on a MyHOMEServer1 (15.2 s shutter), 50 % → 51 %:

  • UP written at +0.00 s
  • direction echo at +0.49 s
  • HA's stop written at +0.93 s, 0.4 s after the echo
  • booked: 0.4 s (53 % from 50 %)

If the stop takes as long to reach the relay as the direction frame took to produce its echo (~0.5 s), every timed run books about 0.5 s less than the motor ran. On a 15 s cover that is ~3 % per run.

Proposal

When the stop status arrives after our own stop write, end the run there instead of at the write, and re-anchor the position from stop status - start anchor.

Not in #702 because it touches the stop path of every timed cover, not only the floor.

What is missing

  • The timestamp of the stop status after HA's stop write, from a debug log, to see how large the gap is. If the stop status follows the write by about the same ~0.5 s, the correction is real; if it arrives almost at once, the current write-time end is fine.
  • Gateways that do not relay the stop status must keep the current behaviour (end at the stop write).

Related: #466, #647, #702

Activity

  1. gdluck commented on Oct 15, 2026

    @gdluck

    Data point from an F461 (firmware 2.0.11) with an F411/2 shutter (5.1 to 5.9 s end stop to end stop), two runs of the same sequence today, timestamps taken on the client at the socket write:

    • the actuator's stop status *2*0*05## follows Home Assistant's stop write by 0.064 to 0.120 s (16 stop writes over the two runs: 0.087 / 0.064 / 0.070 / 0.070 / 0.087 / 0.086 / 0.080 / 0.089 and 0.081 / 0.090 / 0.070 / 0.071 / 0.095 / 0.103 / 0.070 / 0.120);
    • the direction echo *2*1*05## / *2*2*05## follows the direction write by 0.13 to 0.23 s (34 writes, one 0.71 s outlier when the ACK itself took 0.64 s).

    So on this gateway family the write-time end is within ~0.1 s of the real stop (about 2 % of a 5 s run), and the ~0.5 s gap measured on the MyHomeServer1 does not apply. If the correction is implemented, the F461 would sit in the "stop status arrives almost at once" branch. The timed capture (issues_probe.jsonl, writes with write/ACK times and every following event) can be added to the trace corpus if useful.

  2. GreenGrassBlueOcean commented on Oct 15, 2026

    @GreenGrassBlueOcean
    ContributorAuthor

    @gdluck Thank you very much for capturing and sharing these timing measurements on the F461 + F411/2 plant!

    The 64–120 ms stop latency (vs the ~480 ms observed on MyHomeServer1) is a really valuable benchmark for gateway variance across the Legrand family, and confirms that #707's dynamic stop status re-anchoring correctly adapts to fast-echo gateways.

    We would love to add your issues_probe.jsonl trace file to our test fixture corpus (under tests/fixtures/traces/issue_705/) alongside the trace from #714. Could you share or attach issues_probe.jsonl here (or in a gist / PR)? We'll wire it into the replay test suite.

  3. Interstellar0verdrive commented on Oct 17, 2026

    @Interstellar0verdrive
    Member

    The missing number, from my MyHomeServer1 (timed shutter, the same one as the 15.2 s case): after Home Assistant writes *2*0*<WHERE>##, the stop status *2*0*<WHERE>## follows the write by 34 to 47 ms (15 stop writes today, median 42 ms), and it is the only status that follows a stop. The integration's debug log and the bus monitor give the same times.

    So the ~0.5 s I measured is the direction side only: the direction echo *2*1*<WHERE>## comes 0.48–0.49 s after the direction write, while the stop status is practically immediate. On this gateway too, the write-time end is within ~0.05 s of the status, as @gdluck found on the F461 (64–120 ms). I never measured a ~480 ms stop latency, and I would not use that figure for the MyHomeServer1.

    Two consequences for #707:

    • the dynamic re-anchor on the stop status is harmless here (it moves the end by ~0.04 s);
    • the fixed fallback of 0.55 s for gateways that relay no stop status is not backed by any gateway measured so far; both families measured are under 0.12 s. A smaller fallback, or none, would match the data.

    One caveat that applies to both measurements: a stop status 40 ms after the write is most likely the gateway relaying the command, not a confirmation that the relay contacts opened. The bus cannot tell the two apart, which is also why the start side keeps a motor-start delay. If the run really does book short, the missing time is on the start side (relay pick-up after the echo), not on the stop side.

  4. added 2 commits that reference this issue on Oct 17, 2026
  5. GreenGrassBlueOcean commented on Oct 21, 2026

    @GreenGrassBlueOcean
    ContributorAuthor

    Resolved in PR #707 (6135ae59) and verified with live hardware traces in PR #753 (0f7ae38d), incorporating the stop-status latency measurements from both F461 (@gdluck) and MyHomeServer1 (@Interstellar0verdrive).

Sign up for free to join this conversation on GitHub. Already have an account? Sign in to comment

Metadata

Metadata

Assignees

No one assigned

    Labels

    No labels
    No labels

    Type

    No type

    Projects

    No projects

      Milestone

      No milestone

      Relationships

      None yet

      Development

      No branches or pull requests

      Issue actions