Energy Manager — Integration

A Home Assistant integration that calculates the PV surplus and switches loads automatically by priority.

It is the counterpart to the Energy Manager Card: the card displays and allows manual operation, the integration decides and switches. Both use the same formula — otherwise the display would claim something other than what actually happens.

Status: under development. The automation switches, but has not yet been observed over a longer period on a real installation. The main switch is deliberately off after setup — observe first, then arm it.

Installation

Requires Home Assistant 2025.2 or newer (config subentries).

HACS

  1. HACS → ⋮ menu → Custom repositories
  2. Add https://github.com/eltomato89/EnergyManagerIntegration, category Integration
  3. Install "Energy Manager", restart Home Assistant
  4. Settings → Devices & Services → Add integration → "Energy Manager"

Manual

Copy the folder custom_components/energy_manager to /config/custom_components/ and restart Home Assistant.

Setup

  1. Choose the meter source: a bidirectional grid sensor (>0 import, <0 export) or separate sensors for production and house consumption. That is all the main setup asks for — everything else is added afterwards, one subentry at a time.

  2. Add loads — one at a time via "Add subentry" on the integration entry. Only the switch entity is mandatory; a power sensor, the rated power and the timing fields make the decision more precise.

    If the rated power is missing, the integration estimates it from the recorded statistics of the power sensor: the maximum of the last seven days, refreshed once a day. The mean is unsuitable for this — it would include every hour in which the device was off. If that is not possible either (no power sensor, no recording, sensor without state_class), a default of 500 W applies, and that is almost always wrong.

    The required_source attribute on the status sensor tells you where the value comes from: min_power, max_power, measured, estimated or default.

  3. Add a battery if there is one — likewise via "Add subentry", subentry type "Battery". It is optional, and there may be more than one. See "The battery" below for what it does and what it deliberately does not do.

  4. Observe. The surplus sensor should match the installation and the load states should be plausible. If something is off, the configuration is wrong — not the calculation.

  5. Only then turn on the main switch.

The Energy Manager Card from v0.4.0 finds the integration on its own and displays everything. Loads are maintained here only.

Versioning

Card and integration are versioned independently; the numbers are deliberately not kept in lockstep. What the two sides share is the attribute contract, not the release cadence: releases on one side alone are routine, and the card probes for attributes rather than versions, so an older integration means less display, never an error. Where a card feature does require a minimum integration version, the interface contract lists it. That document is the single place where cross-repository decisions are recorded.

Safety nets

The integration intervenes in a real installation. Six mechanisms prevent it from doing so at the wrong moment — each one closes a case that would otherwise show up as oscillation or as a wrong switching decision:

Protection Against what
At most one switching action per run Switching on three devices at once would mean spending the same budget three times
Anticipation Seconds pass between switching on and the meter showing it. In that gap the same surplus would be handed out a second time
Settling window (default 60 s) After a switching action that device is left alone, whatever the surplus does. Choose it at least as long as the power sensor needs — sluggish smart plugs report only after minutes
Smoothing (default 60 s) A passing cloud is no reason to switch off. While the averaging window is only half filled, nothing is switched at all
Nothing during startup While HA boots, not every entity reports a state — the installation would look as if everything had failed
Nothing with an unusable sensor A kWh meter or a failed sensor is a configuration error, not a surplus of 0 W

In addition, each load has the four timing fields (turn_on_delay, turn_off_delay, min_runtime, min_off_time) and its own automation switch.

When someone else switches

Switching that did not come from this integration is recognised from the service call context — at the device, in the interface, or from another automation. With a manual override time set, the automation then keeps away from that load for the configured period.

The default is 0, which means off, and that is deliberate: whether an override makes sense depends on the device class, not on the user. A dehumidifier never switches itself; a hot water tank cycles, and for it every detection would be a false one. A value that is right for the one and systematically wrong for the other does not belong in a default for all. The last_foreign_change attribute shows how often the case actually occurs for a given device.

The automation switch is never written by the integration. It stays user configuration — and because the override is time-limited, a false detection expires by itself instead of leaving a load out of the automation until someone notices.

Modulating loads

A load can be modulating: instead of only being switched on and off, its power is set in steps through a control entity — a number in W, kW or A, or a select.

The step grid is read from that entity on every evaluation, not configured: min, max, step and the unit for a number, options for a select. Only what Home Assistant cannot know is configured — the number of phases for a control entity in amperes, and the watt value of each option for a select. Reading it fresh each time is deliberate: some wallbox integrations narrow their maximum while charging, and a cached grid would throw that away.

A missing unit is refused, and that is stricter than for a power sensor, where watts are assumed. An ampere entity read as watts would yield a ladder from 6 to 16 W that fits into any surplus — and the automation would write 16 while the device draws 16 A.

The number of phases is not a constant. A wallbox switched between single- and three-phase changes the power of every current step by a factor of three, and a ladder built on the wrong number is off by exactly that. If the device reports its phase count, point phases_entity at it and the ladder follows; the fixed field is then only a fallback. A plain number is expected — devices with their own dialect (go-e reports the phase mode as 0, 1, 2) need a template sensor in front, by the same rule as the switch entity.

Three more fields per load: a minimum level below which the load is switched off rather than throttled (the minimum of the control entity is the limit of the charging station, not that of the vehicle), a hold time between two level changes, and the existing hysteresis, which also acts as the deadband below which no level change happens.

If a device does not reach the level it is asked for, its ladder is capped at what it actually draws, one step above the observed maximum. Without that the priority cascade would permanently reserve the difference for a load that never claims it.

When the device has no switch entity

The switch entity stays mandatory and separate — for a wallbox, 0 is not on the ladder at all, since the charging current starts at 6 A and charging cannot be stopped through it.

Not every device offers a plain switch. A select for the charge release, or a control entity whose 0 means off, are both common. Wrap them in a template switch rather than expecting the integration to learn every device's dialect:

# Charge release is a select (go-e: 2 = charge, 1 = off)
switch:
  - platform: template
    switches:
      wallbox_release:
        value_template: "{{ states('select.goe_XXXXXX_frc') == '2' }}"
        turn_on:
          action: select.select_option
          target: { entity_id: select.goe_XXXXXX_frc }
          data: { option: "2" }
        turn_off:
          action: select.select_option
          target: { entity_id: select.goe_XXXXXX_frc }
          data: { option: "1" }

Where 0 on the control entity means off, the template switch needs a guard. The integration sets the level before switching on, so that the device does not start at the previous, possibly highest step — a turn_on that writes a fixed value would overwrite exactly that:

      heater_release:
        value_template: "{{ states('number.heater_set_output') | float(0) > 0 }}"
        turn_on:
          # Only if nothing is set yet. Otherwise this would discard the level
          # the automation has just written.
          - if: "{{ states('number.heater_set_output') | float(0) <= 0 }}"
            then:
              - action: number.set_value
                target: { entity_id: number.heater_set_output }
                data: { value: 500 }
        turn_off:
          - action: number.set_value
            target: { entity_id: number.heater_set_output }
            data: { value: 0 }

One controller per device

A device that regulates on surplus by itself must not also be managed here. Two control loops on the same load work against each other, and the safety nets above are built for a slow allocator, not for a fast controller: 60 s of smoothing and a 60 s settling window are exactly what a controller must not have.

This applies to wallboxes with a built-in PV mode, to zero-export controllers driving a heating element, and to a second energy manager. Either switch off the other side's regulation, or leave that load out of this integration.

What priority means

It determines two things:

  1. Who is served first when surplus becomes available.
  2. Who has to give way to whom if they would otherwise never get a turn.

The second point is the important one. An example: 800 W of surplus and three loads requiring 1000 W, 500 W and 200 W, in that order of rank. The first one does not fit, so the second and third turn on. If the surplus rises to 1100 W, only 400 W are free — the most important load would never run, even though the installation has long been delivering enough.

Therefore: if available surplus + the load of the running, lower-priority consumers is enough for a more important one, those give way. As few as possible give way, the least important first, and only if it is actually sufficient in the end — otherwise you would have switched things off and gained nothing.

Turning down comes before turning off. A modulating load first gives up only the difference down to its smallest level and keeps running. If that is not enough taken together, a second pass turns throttling into switching off — again from the bottom, and only as far as needed. The status sensor counts both separately: throttles is how many would turn down for a given load, displaces how many would go off.

Not displaced is anything working through a minimum runtime (a wash cycle in progress is not aborted), anything not participating in the automation, anything under a forced run, and anything just switched. A minimum runtime does not prevent throttling, though: it guards against switching a device off too early, and a throttled device keeps running. What does apply to throttling is the hold time between two levels — a displacement is no reason to move the ladder faster than that.

Daily targets

A load can be given a daily target: what it has to achieve per day regardless of the weather. A pool pump has to complete its circulation whether the sun cooperates or not.

The rule is a comparison, not a control loop: once the remaining forecast no longer covers the energy still missing, the load keeps running without surplus. Not before — as long as it works out with sun, there is no reason to take grid power.

The unit follows from the control method: hours for a switchable load, kilowatt-hours for a modulating one. Hours are not a statement for a modulating load — six hours at the lowest level and six at the highest differ by a multiple and satisfy an hours target equally well. Internally everything is kilowatt-hours; hours are only an input and display form.

Two prerequisites: an energy meter on the load, and a forecast sensor with the PV energy still expected today (set in the integration options). Without the forecast the rule never applies — a missing value is a configuration error, not a reason to run a device on grid power.

The day starts at sunrise, not at midnight. For an installation whose yield depends on the sun, that is the cut that fits: a counter reset at midnight lies hours before the first yield and separates nothing.

This is the only place where the automation deliberately accepts grid power, and the must_run attribute says when it does — the answer to "why is that drawing from the grid".

The battery

A battery is a subentry of its own, added through "Add subentry" like a load and shown as its own device. There may be more than one.

It is never switched. The integration sends a battery no command at all — it reads it and takes it into account in the order. That is why its form asks for no switch entity and no control entity: every field there describes a measurement or a limit, none of them an intervention.

A battery therefore needs at least one entity that says something about it: a state of charge, a bidirectional battery power, or separate charge and discharge power. Without one the form refuses it — from numbers alone there is no telling whether the battery is charging or whether it is full, and the order needs both.

Several batteries are added up in the surplus calculation: what flows into them is divertible power, and whether it goes into one or into two changes nothing about that. Each brings its own rule for how discharging counts — one battery may sit at the house connection and another behind a meter of its own, and that is a property of the connection, not of the installation.

Two things still work with the first battery only: the charging-priority threshold and the state of charge reported at the surplus sensor. Both are being reworked; per battery the reliable figure is on its own status sensor.

Whether the house consumption sensor already contains the battery charging stays with the meter, in the main setup, not with the battery: it describes what that sensor measures, and it would be the same statement no matter how many batteries are behind it.

The battery as a shiftable load

Enter a maximum charge power for a battery and it joins the priority order as a load of its own. Loads ranked above it are served first and stay on; the battery then reserves up to its charge power at its rank; only what is left goes to loads ranked below it. When the battery is full it reserves nothing. This is pure scheduling — nothing is switched, only withheld; a number.<name>_priority holds its rank, draggable in the card like any load. Leave the charge power empty (the default) and the battery stays what it was: a correction term in the surplus, with every load ranked ahead of it. That entity is then not created at all, since a rank nothing reads would look like a setting.

Charging priority, adjustable

Below a given state of charge, charging the battery takes precedence: no surplus is reported to the loads at all. That threshold is not a property of your system — it changes with the day. With a very good forecast you may want the loads to start in the late morning at a low state of charge; on an overcast day you may not.

It is therefore a number.<name>_min_soc entity rather than a form field, and an automation can set it like any other number:

# Lower the threshold when a lot of yield is still expected today
action: number.set_value
target:
  entity_id: number.hausbatterie_min_soc
data:
  value: 20

The actual entity ID follows the name of the battery, since Home Assistant derives it from the device name: a battery called "Hausbatterie" gives number.hausbatterie_min_soc.

0 switches the rule off — every state of charge is then above the threshold, which is the behaviour of an installation that never set one. Without a state-of-charge sensor the entity is not created: the threshold would have nothing to compare against, and a control that does nothing is worse than no control at all.

Upgrading from an earlier version

Nothing has to be entered again. A battery that was configured in the main entry moves into a subentry named "Hausbatterie" on the first start after the update — its fields and any threshold already set are carried over — and its two controls move to the new device with it.

Their entity IDs are kept through that move: a threshold that was number.energy_manager_battery_min_soc still answers to that ID at its new device. Home Assistant derives an entity ID from the name only when the entity is first created; afterwards it is a value of its own and survives both the change of device and the new internal key. Dashboards, automations and history therefore keep working, even though the ID no longer matches the name of the device it now hangs on. Renaming it is a decision for you — taken here, it would break every reference to the old ID without asking.

Why is nothing happening?

The most common question — and without an answer, an absent switching action cannot be told apart from a fault. Two places provide it:

The automation status sensor (sensor.…_status) for the whole:

Value Meaning
starting HA is still booting, or the averaging window is too sparsely filled
sensor_error A meter sensor is missing, has failed, or does not measure power
paused Main switch off
running Everything ready

The status sensor of each load in its blocked_by attribute for the individual case:

Value Meaning
not_managed The automation switch of that load is off
unavailable The switch entity reports no state
settling The settling window after the last switching action is running
forced A forced run is active — the automation keeps away
manual Someone else switched this load — the automation keeps away for the configured time
turn_on_delay / turn_off_delay The condition has not held long enough yet
min_runtime / min_off_time A lockout is running, see "locked until"

If nothing is listed there, the surplus is simply not sufficient — which the load state then says (off_close, off_insufficient).

What the integration provides

One hub device, one device per load, one device per battery:

Hub

Entity Purpose
switch.…_automation Main switch. Off means: nothing is switched
sensor.…_surplus Available surplus after reserve and state-of-charge rule
sensor.…_surplus_unsmoothed Unsmoothed raw value, for diagnosis
sensor.…_status State of the automation

Per load

Entity Purpose
switch.<name>_automation Does this load participate in the automation?
number.<name>_priority Rank, 1 = highest
sensor.<name>_status Load state, same values as in the card
sensor.<name>_locked_until When the lockout ends — exact, not estimated

Per battery

Entity Purpose
sensor.<name>_status Battery state, same values as for a load, plus state of charge, rank, reserved power and whether it is full
number.<name>_priority Rank as a shiftable load — only when a maximum charge power is set
number.<name>_min_soc Charging-priority threshold — only when a state-of-charge sensor is set

A battery has no automation switch and no lockout sensor. Neither would have anything to act on: it is never switched, so there is nothing to leave alone afterwards.

No helper variables are required. The card reads and operates these entities directly.

The entity IDs above follow the language of your Home Assistant instance, because HA derives them from the translated entity name. On a German instance the same sensors are called sensor.…_ueberschuss and sensor.<name>_gesperrt_bis. The card does not rely on the IDs; it identifies the entities by their role.

Services

Four services for what cannot be expressed through entities alone: a duration. The main switch only knows on and off.

Service Purpose
energy_manager.force_on Switches a load on immediately and keeps it running for the given time, regardless of surplus. Works even with the main switch off, since this is an operation rather than an automation decision
energy_manager.clear_force Ends a forced run early. Nothing is switched off; from then on the surplus decides again
energy_manager.clear_manual Ends a manual override early. Nothing is switched; from then on the surplus decides again
energy_manager.pause Stops the automation, optionally for a set time ("two hours of quiet", during maintenance for instance)
energy_manager.resume Arms it again

force_on and clear_force target a load device; an entity of the same device works just as well, since an automation usually has an entity_id at hand.

action: energy_manager.force_on
target:
  device_id: <wallbox>
data:
  duration: "01:30:00"

Development

uv venv --python 3.13
uv pip install -r requirements_test.txt
.venv/bin/python -m pytest tests/ -q
.venv/bin/python -m ruff check . && .venv/bin/python -m ruff format --check .

The calculation core (surplus.py, smoothing.py, engine.py) is a port of the card logic and is verified against the same test cases. A differing result is a bug — not an acceptable deviation.